FOXBORO FMB242 Field Device System Integrator Module
-
Warranty: 365 days
Quality: Original module
Condition: New / Used
Warehouse: Spot
Delivery time: Shipped in 3 days after payment
Mail: 3598571032@qq.com
Phone/Wechat/Whatsapp:+86 15339539190
-
Details
Product details
Origin:USA
Brand:FOXBORO
Product ID: FMB242
product description
Field Device System Integrator Module
OVERVIEWA
pair of FBM231 modules combine to provideredundancy at the Fieldbus Module
(FBM) level, withfield wiring to two termination assemblies (seeFigure 1). In this
configuration, one FBM231 is theMaster, and the other is the Tracker module.
Inputpoints on the control station are updated from thedevice inputs received on
the network connected tothe Master. Device output points, depending on theI/O
driver, are written by both the Master and Trackermodule. Role switching is automatic
if actualproblems are detected (for example, heartbeat) bythe I/O driver, or the
user can switch the roles at anytime via SMDH.The FBM231 has four ports - each
can beindividually configured in software for RS-232,RS-422 or RS-485. This allows
a single FBM231the flexibility to connect to multiple similar but notidentical devices.
Ports 1, 2, 3, and/or 4 can beconfigured as a single logical port with redundantcables
allowing you to interface with dual-ported I/Odevices within your plant. The general
networkconfigurations are shown in Figure 1.
The FBM231 and its associated terminationassemblies (TA) accommodate several
types ofconnections to dual-ported devices; directconnection to devices; connection
to modems whenused with the RS-232 communication interface, andmultidrop connections
to RS-485 devices. Intrinsicsafety devices can be connected between the TAand the
field device. For single ported devices, youshould use the FBM230.
FEATURES
The key features of the FBM231 are:
Redundant FBM231 modules communicate withdual-ported devices
Four ports - each can be individually configured insoftware for RS-232, RS-422 or RS-485
Supports RS-232, RS-422 or RS-485communication interface standards
I/O software driver is downloadable from a libraryof available protocols.
Up to 2000 DCI block connections
Communicates with up to 64 RS-485 or up to 4direct connect RS-232 or RS-422 devices
Integrates field device data into a Foxboro controldatabase
Field mounted
Class G3 (harsh) environments